SC-120W series UPS function monitor power supply
Features:
·AC input voltage range selected by switch
·Small volume,low weight,high efficiency
·Protections:short circuit/over load
·Indicator for power on/charge/normal(LED)
·100% full load burn-in test
·Battery protection at low voltage
·2 Year warranty
Model |
SC-120-12 |
SC-120-24 |
|||
output |
DC voltage |
CH1:13.8V |
CH1:13.4V |
CH1:27.6V |
CH2:26.5V |
Voltage tolerance |
±1% |
----- |
±1% |
----- |
|
Rated current |
8A |
0.5A |
4A |
0.3A |
|
Current range |
0~8A |
----- |
0~4A |
----- |
|
Rated power |
117.1W |
118.4W |
|||
Ripple&noise |
120mvp-p |
----- |
180mvp-p |
----- |
|
DCvoltage ADJ.range |
CH1:11.3~14.9V |
CH1:21.3~29.8V |
|||
input |
Voltage range |
90~264VAC,127~370VDC |
|||
frequency |
47~63HZ |
||||
AC current |
2.8A/115VAC,1.4A/230VAC |
||||
efficiency |
81% |
83% |
|||
Inrush current |
Cold start current 30A/115VAC,50A/230VAC |
||||
Leakage current |
< 1mA/240VAC |
||||
protection |
Over load |
Rated output power110%~150% start over load protection |
|||
protection mode: AC charging mode:hiccup mode auto-recovery after fault condition is removed |
|||||
Batteryprotection At low voltage |
9.5~11V |
20~22V |
|||
protection mode:cutoff output |
|||||
Function |
UPS introduction |
long-term online floating charge to battery,high charging efficiency,battery can saturate to more than 90% ,cauto-stop harging when it's full,prevent over charging. Effectively extend battery life,AC/battery auto switch,no switch time,no need human guard, cold-start ,when there is no AC input ,can use battery start UPS,Meet the user's emergency needs |
|||
environment |
Working temp,humidity |
-10℃~+60℃,20%~90%RH |
|||
Storagetemp,humidity |
-20℃~+85℃,10%~95%RH non-condensing |
||||
Withstand vibration |
10~500HZ,2G10min/1cycle,period for 60 minutes,each axes |
||||
safety |
Withstand voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
|||
Isolated resistance |
I/P-O/P,I/P-FG,O/P-FG:100Mohms/500VDC |
||||
Fitstandard |
Safety standard |
Compliance to UL60950-1 |
|||
EMC standard |
Compliance to EN55022,CLASSB |
||||
others |
Dimension |
159*97*38mm(L*W*H) |
|||
Weight/packing |
0.56kg/45pcs/26kg/0.041m³/1.45CUFT |
||||
note |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and25℃of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. |