DR-240W series Din-rail power supply
Features:
·AC input voltage range selected by switch
·Small volume,low weight,high efficiency
·protections:short circuit/over load/over voltage/over temp
·cooling by free air convection
·can be installed onDINrail:TS-35/7.5or TS-35/15
·LED indicator for power on
·100% full load burn-in test
·2 Years warranty
Model |
DR-240-24 |
DR-240-36 |
DR-240-48 |
|
output |
DC voltage |
24V |
36V |
48V |
Voltage tolerance |
±1% |
±1% |
±1% |
|
Rated current |
10A |
6.6A |
5A |
|
Current range |
0~10A |
0~6.6A |
0~5A |
|
Rated power |
240W |
237.6W |
240W |
|
Ripple&noise |
120mvp-p |
150mvp-p |
180mvp-p |
|
DC voltage ADJ.range |
±10% |
±10% |
±10% |
|
input |
Voltage range |
90~132VAC/180~264VAC,255~373VDC |
||
frequency |
47~63HZ |
|||
AC current |
2.8A/110VAC,1.4A/220VAC |
|||
efficiency |
85% |
85% |
86% |
|
Inrush current |
Cold start current 27A/110VAC,45A/220VAC |
|||
Leakage current |
< 3.5mA/240VAC |
|||
protection |
Over load |
Rated output power105%~135% start over load protection |
||
protection type :rated current limit,auto-recovery after fault condition is removed |
||||
over voltage |
30.6~33.2V |
42.6~44.2V |
54.8~56.6V |
|
protection type:cutoff output,recovery after restart power |
||||
over temperature |
TSW1detect on heatsink of power transistor≥105℃±5℃, start over temperature protection |
|||
Protection mode:cutoff output,auto-recovery after temperature become normal |
||||
environment |
Working temp,humidity |
-20℃~+60℃,20%~90%RH |
||
Storage temp,humidity |
-40℃~+85℃,10%~95%RH non-condensing |
|||
Withstand vibration |
10~500HZ,2G10min/1cycle,period for 60 minutes,each axes |
|||
safety |
Withstand voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
||
Isolation resistance |
I/P-O/P,I/P-FG,O/P-FG:100Mohms/500VDC |
|||
Fit standard |
Safety standard |
Compliance to UL1012 |
||
EMC standard |
Compliance to EN55022,CLASSA |
|||
others |
Dimension |
125.5*125.2*100mm(L*W*H) |
||
Weight/packing |
1.2kg/12pcs/15.5kg/0.046m³/1.64CUFT |
|||
note |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and25℃of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. |
如果您有任何关于合作的报价或有任何查询,请随时给我们发电子邮件 info@hwele.net或使用下面的查询表格。我们的销售代表将在24小时内与您联系。感谢您对我们的产品感兴趣。